Project  : Sour water treatment Service
Owner  : PT. Pertamina RU III Plaju
Location  : Palembang, Indonesia
Treatment Capacity  : 5 m3/day

Description

Plasma treatment to treat Sour Water from Oil & Gas Refinary

Parameter that must be achieved:

Comply with Indonesia DOE regulatory limits
BOD, COD, Sulfide (as H2S), Phenol, Total Ammonia, pH

Table Plugin
Result
Regulatory Limit Waste water ex Boiler Waste water ex CDU group Waste water ex FCCU group
Debit 4,4 10,9 24,7
BOD5 80 20 42 55
COD Cr 160 90 122 96
Sulfida (as H2S) 0.5 0.01 0.2 0.2
Phenol 0.5 0.01 0.4 0.3
Ammonia total 5 1 2 4
pH 6-9 8.4 7.5 7.5
Table Plugin